Have you ever wondered what
the size of your imager’s field of view
is at a given distance? If you know the visual
field of view specifications for a thermal imager,
it is possible to calculate the size of your
imager’s viewing area for any given distance
using a scientific calculator. The formula for
this calculation is:
{(tangent 1/2 viewing angle)
x distance} x 2
To apply the above formula,
follow these steps:
1. Determine your imager’s
Field of View (in degrees) from the manufacturer’s
specs.
2. Divide the value from Step
1 by 2
3. Use scientific calculator
to determine tangent of number obtained in Step
2
4. Multiply number in Step 3
by distance from imager lens to object.
5. Multiply number in obtained
in Step 4 by 2. This will be the width of the
imager’s field of view at the specified
distance.
Example: Calculate field of
view for 16° lens at 25’.
(tan 8° x 25’) x 2
=
(0.140541 x 25’) x 2 =
(3.513525’) x 2 = ˜ 7.0’
If your imager specifies
different Field of View values for horizontal
and vertical, it will be necessary to calculate
each value separately. Calculated values should
be used for estimation purposes as actual values
may vary slightly.
January
20, 2003
Sponsored
by:
Easier
Than A, B, C
When performing infrared inspections
of electrical distribution systems, many people
identify the individual phases of polyphase circuits
as A, B, and C; others frequently use 1, 2, and
3.
Confusion can arise with alphabetical
or numerical labels particularly when switchgear
enclosures are inspected from different perspectives
e.g. front versus rear. Further confusion can
occur when phase rotation has been modified or
changed or, in some cases, mislabelled.
Reference errors can be avoided
by using terms that cannot be confused such as
Left, Middle, Right OR Upper, Middle, Lower.
When using such terms, one should always reference
where the image was taken from. For outside power
lines references such as Street, Center, and
Field may be used to identify phases without
confusion.
Using the above simple
terms can make your reports easier to understand
and help to eliminate confusion when repairs
are performed.
January
27, 2003
Sponsored
by:
Pipe
Leaks in Concrete
Thermal imging can often be
used to help locate leaks from pipelines buried
within concrete. For best reults, the subject
piping should be heated as much as possible prior
to imaging. Cold water lines may be heated by
continuously flushing them with hot water. The
amount of time required will depend upon the
burial depth of the lines and the thermal conductivity
of the concrete.
Once the lines have been heated,
use your thermal imager to inspect the pathway
of the pipe. Pipe leaks will appear as amporphously
shaped warm areas instead of the well-defined
lines caused by the pathway of the pipe. Suspected
leaks may be marked directly on the concrete
to direct excavation efforts required for leak
verifcation and repair.
When imaging outdoors, it is
best to perform infrared imaging at night to
avoid interference from the sun.
Translated from tip submitted by Juan Nava,
Cemex Mexico Planta Hermosillo.
Gracias Juan!
February
2, 2003
Sponsored
by:
The
3 Most Important Questions
Thermal anomalies are not always
as obvious as one might expect. Often, subtle
thermal differences can be indicative of major
problems. Because infrared thermography is a
visual inspection technique, its effectiveness
relies on the observation skills of the thermographer.
Like any visual inspection technique, a thermographer
must actively concentrate on the imagery displayed
by their thermal imager.
Contrary to popular belief,
humans are not inherently effective observers.
Because humans tend to be casual in their observations,
they frequently overlook subtleties. Whenever
imaging, a thermographer’s eyes should
always visually scan the monitor left to right
and up and down while asking him/herself the
following three questions:
1. What am I seeing
2. Why am I seeing this
3. Is this normal/reportable
While this approach may
sound cumbersome at first, this practice will
soon become instinctive and can help prevent
you from overlooking the subtle thermal patterns
that can be indicative of serious problems.
February
10, 2003
Sponsored
by:
Power
Alternatives for Imagers
Traditionally, storage batteries
for thermal imagers have been proprietary and
available only from the imager manufacturer.
Often, these special battery packs have cost
hundreds of dollars each.
With a moderate amount of electrical
skill and some homework, there are affordable
power alternatives to be found in commercially
available battery packs. To use an alternative
battery, do the following:
1. Determine the required voltage
of your imager.
2. Use a DC ammeter to determine
the imager current requirements. If you know
your imager’s power consumption in Watts,
divide this number by the voltage required by
your imager. Example: An imager that uses 12
Watts at 6 volts will draw 2 amps of current.
3. Select a battery with appropriate
voltage and capacity. To determine how a battery
will last with your imager, divide the Amp Hour
rating by the current draw of your imager. A
wide variety of rechargeable batteries are available
through many professional video retailers.
4. Construct a fused power cord
to connect your imager to your power supply making
sure that the polarity is correct.
Constructing your own
battery packs can save you money and result
in longer run times between battery charges.
February
17, 2003
Sponsored
by:
Setting
Up Inspection Routes
Proper planning prevents poor
performance. This frequently repeated phrase
has been applied to many disciplines and has
application in thermography as well. One of the
greatest appeals to thermography as a PdM tool
is the wide range of potential applications.
However, without planning the varied uses for
thermography can cause one to lose focus and
compromise program efficiency.
Using preplanned routes can
improve inspection efficiency by serving as a
roadmap for your inspection activities. When
setting up inspection routes, keep the following
in mind:
1. When possible, use established
routes from other PdM technologies such as vibration
analysis.
2. Routes should be of same
class or hierarchy for subject equipment. As
an alternative, establish routes based upon physical
location.
3. Keep in mind requisite travel
times between locations.
4. Establish routes to ensure
that subject equipment will be under proper load.
5. Never include more equipment
in a route than can be accomplished in a single
work shift.
When following a route
during an inspection, any equipment not inspected
should be noted in the final project report.
March
3, 2003
Sponsored
by:
The
Tortoise and the Hare
Everyone has heard the fabled
race between the tortoise and the hare in which
the tortoise beats the hare. One of the morals
of the story is that a steady pace may be more
fruitful than erratic bursts of speed.
Thermographers who perform infrared
inspections should keep in mind that a slow and
steady pace can lead to victory. Working at an
even pace can help to prevent overlooking the
subtle temperature variations that often indicate
serious problems. Purchasers of thermographic
services should bear in mind that the best value
is not in the fastest inspection time, but rather
in the thoroughness and accuracy of the inspection.
When it comes to your
next infrared inspection, beware of the hare.
Inspections that are praised more for their
swiftness today may be cursed in the future
for their costly oversights.
March
10, 2003
Sponsored
by:
When
Will They Die
Nearly all portable thermal
imagers designed for predictive maintenance utilize
storage batteries as a power source. As such,
even the best thermographers are limited by the
storage capacity of their batteries. When planning
a project it is helpful to know how long your
batteries should last.
Most batteries sold are rated
in Amp Hours, a number used to indicate battery
supply capacity. To determine how long a battery
will last with your imager, divide the Amp Hour
rating of the battery by the current draw (in
Amps) of your image. For an imager that draws
2 Amps, a 6 AH battery will last 3 hours.
Depending upon their size, some
batteries are rated in milliAmp Hours. To convert
this number to Amp Hours, divide the mAH rating
by 1000. Example: An 1800 mAH battery equals
1.8 AH
It is important to know
that some imagers consume more power during
start up. If so, this will shorten the expected
run time of a battery from the calculation
above. A battery’s storage capacity also
decreases with age. If your batteries are providing
extremely short run times, it may be time to
replace them with new ones.
March
17, 2003
Sponsored
by:
Spots
on the LCD Screen
If you have inactive spots on
the LCD screen in your infrared camera's monocular
viewfinder, they are probably caused by sun damage.
When working outdoors, sunlight
can easily enter an upturned viewfinder eyepiece.
When this happens, sunlight can be magnified
by the viewfinder optics permanently damaging
or destroying your LCD screen.
To prevent such damage, always
cover your imagers eyepiece to prevent sunlight
from entering the viewfinder. Temporarily placing
a cover such as a baby sock over the eyepiece
until you are ready to image can help to avoid
a ruining an expensive viewfinder.
If you are a thermographer who
performs infrared inspections of electrical distribution
systems, you are not alone and you never should
be. Working alone near exposed, energized electrical
equipment is not only dangerous, it is a violation
of federal law!
Administered by OSHA, the Occupational
Safety and Health Standards for General Industry,
29 CFR, Part 1910 apply to most thermographers
working within the United States or its territories.
Specifically, 1910 Subpart R covers the operation
and maintenance of electric power generation,
control, transformation, transmission and distribution
lines or equipment. Covered facilities include
utilities and equivalent industrial establishments.
According to Subpart R, prior
to the commencement of work, medical and first
aid supplies must be provided for, including
persons trained in first aid and CPR when work
is on or near exposed lines or equipment energized
at greater than 50 volts. Since CPR cannot be
self-administered, at least two people trained
in first aid and CPR must always be present when
working near most exposed energized equipment.
When performing infrared
inspections in the future, having a second
CPR trained person along will not only satisfy
OSHA requirements, it may save your life should
an accident occur!
April
7, 2003
Sponsored
by:
The
Myth Behind IFOV Values
A specification commonly provided
for thermal imagers is Instantaneous Field of
View or IFOV. Many people mistakenly believe
that IFOV values provide meaningful information
about a thermal imager’s performance. Unfortunately,
this is simply not true.
Originally developed for evaluating
the optical performance of thermal imaging systems,
IFOV values were intended to allow a user to
calculate the minimum target size needed to achieve
50% probability of detection at any given distance.
Using IFOV values to evaluate modern thermal
imagers and radiometers is unreliable for several
reasons:
1. To date, there is no accepted
standard for determining IFOV. Consequently,
imager manufacturers calculate IFOV values differently,
making test results impossible to compare.
2. Because IFOV values are reported
for a single pixel, they cannot be used to accurately
calculate spot measurement size for imaging radiometers
since accurate temperature measurement requires
several pixels, not just one.
3. Stated IFOV values are traditionally
reported at 50% radiance or less which is unreliable
for both temperature measurement and accurate
thermal imaging.
When comparing commercial
infrared equipment specifications, one should
simply ignore IFOV values and concentrate on
meaningful specifications instead.
April
14, 2003
Sponsored
by:
Blinded
by the Light
While it is often interesting
to use a thermal imager to view ordinary objects,
imaging the sun, arc welders and similarly hot
objects should be avoided unless your imager
has been built specifically for these applications.
The reason for this is that the sensitive thermal
detector that comprises the heart of any thermal
imaging system can be destroyed by imaging very
hot objects, even for brief periods of time.
To help avoid a costly detector
replacement, only image objects whose temperatures
are within the stated operating range of your
imager.
Perhaps a sage corollary could
be derived from Bruce Springsteen's epic song,
Blinded by the Light:
... Mama always told not to
image into the sights of the Sun...
A ruined detector assembly
is NOT where the fun is.
April
21, 2003
Sponsored
by:
Equipment
Maintenance - Neckstraps
Almost all handheld thermal
imagers come equipped with neckstraps as standard
equipment. If you utilize the neckstrap supplied
with your imager to support or carry your imager,
the following tips can help to avoid costly damage
caused by an unexpected drop.
1) Many neckstraps are made
of relatively thin material. Retrofit thin neckstraps
with sturdier material.
2) Check your neckstrap frequently
for wear. Neckstraps frequently become frayed
where they attach to camera body eyes or snap
hardware.
3) Be certain that your neckstrap
ends are permanently sewn so that they cannot
be pulled apart or separate accidentally.
4) Check snap swivels for condition.
Replace worn or inferior hardware with quality
materials.
5) Consider adding a second,
redundant neckstrap in case the primary neckstrap
fails.
6) Periodically check camera
body eyes for wear and mechanical integrity.
Over time, attachment points that mate with metal
hardware can erode; mechanically fastened hardware
on your imager can become loose.
Following the above tips
can help prevent accidentally dropping your
imager and could save you from a costly repair.
May
5, 2003
Sponsored
by:
Setting
Temperature Limits
Over the past twenty years,
a number of temperature severity guidelines that
have been published by various organizations.
When using these guidelines, you may compare
similar components under similar load to each
other OR compare the subject component to ambient.
The former of these approaches is recommended
since since ambient temperature can swing widely
over time. Furthermore, it is often impossible
to obtain an accurate ambient temperature for
devices located within an enclosure once the
enclosure has been opened for the infrared inspection.
One of the most conservative
temperature guides can be found in the Maintenance
Testing Specifications, published by the
National Electrical Testing Association, Morrison,
Colorado. According to the NETA MTS, temperature
differentials greater than 15° C are categorized
as, "Major discrepancy; repair immediately".
Other organizations publish
less conservative temperature guidelines than
the NETA MTS. Some guides require delta T's
of 70°C or higher to qualify as items of
immediate concern. When setting temerature
limits, one should remember that temperature
differentials cannot be utilized to predict
time to failure for an electrical device. Therefore,
all thermal anomalies detected during an infrared
inspection should be investigated and proper
corrective measures undertaken as soon as possible.
May
12, 2003
Sponsored
by:
Infrared
Inspection of Capacitors
Capacitors are devices commonly
found in AC electrical distribution systems where
power factor correction is required. Like any
electrical component, capacitors need to be regularly
checked for proper operation. Infrared thermography
can be used to rapidly inspect capacitors from
a safe, remote distance.
Capacitors are wound devices
that are electrically connected between potential
and ground. Capacitors used for power factor
correction are generally encased in painted,
rectangular steel canisters and often have two
equal sized bushings for electrical connections.
In a three phase circuit, there may be several
capacitors connected to each phase.
The most common failures of
capacitors are loose/deteriorated bushing connections,
open circuits due to internal winding failure,
and open supply circuits. When inspecting capacitors,
be sure to:
1. Visually inspect capacitor
bodies. Capacitors should not be misshapen/
swollen.
2. Thermographically inspect
capacitor bodies. Capacitors should be warmer
than ambient air temperature and exhibit equal
temperatures across all phases.
3. Check bushing and wiring
connections for hotspots.
Any thermal anomalies
detected should be investigated and corrected
as soon as possible. Capacitors operating at
ambient temperature should be corrected immediately
as imbalanced capacitance can be more detrimental
than having no capacitors at all.
May
19, 2003
Sponsored
by:
The
Problem with Solar Loading
Everyone who has performed infrared
inspections outdoors on sunny days is familiar
with the problem of solar reflections. Compensating
for solar reflections is usually accomplished
by repositioning the thermal imager to change
the viewing angle to eliminate the reflection.
For objects exposed to strong sunlight, a more
insidious problem can occur in the form of solar
loading.
The concept of solar loading
is familiar to everyone: objects exposed to the
Sun will heat up. In general, dark colored objects
absorb the most solar energy and heat faster
than light colored objects. If an object absorbs
enough heat from the Sun, significant thermal
anomalies may be hidden and go undetected.
As there is no way to
compensate or correct for solar loading, the
most prudent course of action is avoidance.
Solar loading can be avoided by imaging on
cloudy days, at night, or early in the morning.
Solar loading can also be overcome by shading
an exposed target and waiting for the object’s
temperature to return to normal.
May
27, 2003
Sponsored
by:
Infrared
Inspection of Capacitors
Capacitors are devices commonly
found in AC electrical distribution systems where
power factor correction is required. Like any
electrical component, capacitors need to be regularly
checked for proper operation. Infrared thermography
can be used to rapidly inspect capacitors from
a safe, remote distance.
Capacitors are wound devices
that are electrically connected between potential
and ground. Capacitors used for power factor
correction are generally encased in painted,
rectangular steel canisters and often have two
equal sized bushings for electrical connections.
In a three phase circuit, there may be several
capacitors connected to each phase.
The most common failures of
capacitors are loose/deteriorated bushing connections,
open circuits due to internal winding failure,
and open supply circuits. When inspecting capacitors,
be sure to:
Visually inspect capacitor
bodies. Capacitors should not be misshapen/
swollen.
Thermographically inspect
capacitor bodies. Energized capacitors should
be warmer than ambient air temperature and
exhibit equal temperatures across all phases.
Check bushing and wiring
connections for hotspots.
Any thermal anomalies
detected should be investigated and corrected
as soon as possible. Capacitors operating at
ambient temperature should be corrected immediately
as imbalanced capacitance can be more detrimental
than having no capacitors at all..
June
2, 2003
Sponsored
by:
The
Weakest Link
We’ve all heard the phrase, “A
chain is only as strong as its weakest link.” When
it comes to thermography, the weakest link is
frequently not the test equipment but rather
the thermographer.
All too often, many facility
managers are led to believe that infrared imagers
are fully automatic instruments that require
nothing more than “point and shoot” operation.
While thermography is a science, it is also an
art or craft requiring a skilled human operator
for both conducting the inspection and interpreting
the data obtained.
In order to achieve maximum
effectiveness, thermographers need to have an
understanding of infrared theory, heat transfer
concepts, equipment capabilities and limitations,
and environmental conditions, as well being knowledgeable
about the system(s) being inspected.
Whether you are setting up an
infrared inspection program or maintaining one,
thermographer training should not be overlooked.
Obtaining quality training is an investment that
can pay huge dividends by maximizing the effectiveness
of thermographers and eliminating your weakest
link.
Infraspection Institute
offers Level I, II, and III training and certification
for thermographers worldwide. Our infrared
training programs meet the requirements for
training of NDT personnel in accordance with
the ASNT document, SNT-TC-1A.
June
9, 2003
Sponsored
by:
Spring
is the Time for IR Roof Inspection
With onset of warmer weather,
the harshness of winter is but a fading memory
for most. Left undetected, the damage caused
by winter’s fury is a reality that can
lead to premature roof failure. Fortunately,
an infrared inspection of your roof can detect
evidence of problems before they can get out
of hand.
Performed under the proper conditions
with the right equipment, an infrared inspection
can detect evidence of latent moisture within
the roofing system often before leaks become
evident in the building.
The best candidates for infrared
inspection are flat or low slope roofs where
the insulation is located between the roof deck
and the membrane and is in direct contact with
the underside of the membrane. Applicable constructions
are roofs with either smooth or gravel-surfaced,
built-up or single-ply membranes. If gravel is
present, it should be less than ½” in
diameter and less than 1” thick.
For smooth-surfaced roofs,
a short wave (2-5.6 µ) imager will provide
more accurate results especially if the roof
is painted with a reflective coating. All infrared
data should be verified by a qualified roofing
professional via core sampling or invasive
moisture meter readings.
June
16, 2003
Sponsored
by:
Applying
Thermography
Thermography is a versatile
nondestructive test technique that has a wide
variety of applications. In short, thermography
can be applied to any situation where knowledge
of heat patterns and associated temperatures
across a surface will provide meaningful data
about a system, object, or process.
In thermography, there are two
basic approaches to evaluating data. Qualitative
thermography or thermal imaging relies on observing
thermal patterns and noting any inexplicable
differences or anomalies. Quantitative thermography
adds non-contact temperature measurements to
thermal images.
Many systems produce heat as
a byproduct of operation. Such systems include
electrical distribution systems, machinery and
insulated structures. These systems are generally
inspected during normal operation once line-of-sight
access is obtained.
Thermography can also be applied
to systems that do not produce heat as a byproduct
of operations by actively heating and/or cooling
the target and observing the resulting images.
Systems that are candidates for active thermography
include building facades, low slope roofing systems,
storage tanks and composite materials.
When heated or cooled
properly, thermal patterns caused by changes
in the thermal conductivity or capacitance
of the subject system can provide evidence
of internal structures, water infiltration,
or contaminants. The use of active thermography
is growing, especially for inspection of composite
materials used in the aircraft, aerospace,
and marine industries.
June
23, 2003
Sponsored
by:
How
Close Do You Need to Be
One of the most frequently asked
questions in thermography is, “How close
do I need to be to my target?” The answer
depends upon target size and the type of data
that are desired.
Appropriate distance is largely
dependent upon three factors: target size, IR
equipment optics, and detector resolution.
With qualitative thermal imaging,
the maximum viewing distance is achieved where
the object and any possible anomalies can be
clearly resolved. If a target cannot be clearly
distinguished, it will be necessary to move closer
or to use a telephoto optic.
When using an imaging radiometer,
obtaining accurate temperatures will require
substantially shorter distances than those required
for thermal imaging. Obtaining accurate quantitative
data requires that the radiometer’s spot
measurement size is smaller than the area being
measured. If it is determined that the radiometer’s
spot size is larger than the area being measured,
it will be necessary to move closer or use a
telephoto optic calibrated for the imager.
Because there is no method
for correcting for errors caused by imaging
at excessive distances from a target, it is
imperative to always ensure appropriate distance
prior to recording images.
June
30, 2003
Sponsored
by:
Infrared
Prior to PM Shutdowns
Many facilities undergo regularly
scheduled shutdowns for preventive maintenance.
Performed prior to shutdowns, infrared inspections
can help to point out potential problems in electrical
and mechanical systems and allow for more effective
use of resources during a shutdown.
When planning a scheduled outage,
it is a good practice to schedule infrared inspections
four to six weeks prior to the outage. Doing
so can uncover hidden problems and allow for
scheduling of additional requisite manpower and/or
obtaining replacement parts prior to the shutdown.
Infrared inspections can also save money by helping
to direct maintenance efforts where they will
be most needed during the planned outage.
Pre-outage infrared inspections
should be performed with subject equipment energized
and operating under normal load. Inspections
should be performed by trained and certified
thermographers who are familiar with the equipment
being inspected.
A follow-up infrared inspection
of all repaired/retrofitted equipment should
be performed within 48 hours of repair or installation
to confirm that repairs were effective.
For more information on
training and certification, or to obtain a
copy of the Guideline for Infrared Inspection
of Electrical and Mechanical Systems, please
contact Infraspection Institute at 609-239-4788
or visit us online at www.infraspection.com.
July
7, 2003
Sponsored
by:
Know
Your Target
When performing an infrared
inspection, obtaining quality data relies on
the use of proper equipment, thermographer training
and knowledge of the system being inspected.
It is imperative that a thermographer be familiar
with the construction and operation of the object(s)
to be imaged before the inspection begins.
Prior to performing an infrared
inspection of an object for the first time, a
thermographer should:
1. Become familiar with system
construction by reviewing appropriate drawings
or blueprints noting insulation materials located
on, or within, the subject system and how they
might impact findings.
2. Discuss with the end user
the reason(s) for conducting the infrared inspection.
3. Review any previous inspection
reports and operational data to determine history
of the subject system including past problems.
4. Ascertain that the system
is under normal operating conditions and how
its operation is likely to affect thermal signatures.
5. Ensure that line-of-sight
access is available and that environmental conditions
and infrared equipment are appropriate for collecting
accurate data.
6. Determine if a similar system
is available for reference purposes.
Following the above can
vastly improve the quality of collected data
and help to reduce errors in reporting. As
always, remember to work safely.
July
21, 2003
Sponsored
by:
Monochrome
or Multi-color?
With most thermal imagers capable
of displaying images in monochrome or multicolor,
many new thermographers ask which color palette
is the best choice for effective imaging. The
answer will depend on a number of factors including
application, delta T associated with the exception,
and personal preference.
Because it is usually less confusing
than multi color palettes, grayscale may be better
suited for some applications. Additionally, applications
that have a large delta T associated with exceptions
or where target recognition is important may
be better suited for grayscale imaging. Such
applications include electrical distribution
systems, building envelopes inspected from the
interior of the structure, and low slope roof
inspections.
Multicolor palettes offer an
advantage when imaging targets having a small
delta associated with exceptions or when imaging
targets with several discrete temperature zones.
Typical applications include mechanical systems,
refractory systems, building envelopes inspected
from the exterior, and medical/veterinary applications.
For hardcopy reports,
printing monochrome images can result in lower
cost than multicolor reports. Lastly, the choice
to use monochrome or multicolor is largely
a matter of personal preference. Thermographers
should always use a palette which best represents
the observed thermal patterns and provides
data that are easily understood.
July
28, 2003
Sponsored
by:
Thermal
Imaging Basics
With tremendous emphasis placed
upon the sophistication of today’s modern
thermal imagers, it’s easy to forget the
basics of thermal imaging. Regardless of imager
age or sophistication, there are several basic
concepts that can vastly increase the accuracy
and success of an infrared inspection.
1. Select the proper spectral
response imager for the application.
2. A clear line of sight to
the target is required with no obstruction of
the imager lens.
3. Imager optics must be clean
and calibrated to the imager being used.
4. Target should be dry and
at a stable temperature.
5. Imager focus is imperative
to accurate diagnosis and temperature measurement.
Be sure to focus imager and the viewfinder as
well.
6. Knowing the construction,
operation and characteristics of the system being
inspected is vitally important to anticipating
thermal patterns and performance.
7. Adverse atmospheric conditions
such as wind, humidity, or solar reflection and
solar loading should be avoided.
8. For electrical and mechanical
equipment, the systems must be energized and
under load; for structural inspections, a delta
T of 10 C (18 F) is desired.
9. Discriminating small temperature
differentials across targets with low emittance
values can prove quite difficult.
10. Whenever safely possible,
cross reference observed infrared temperature
values with accurate contact temperature readings.
When performing any infrared
inspection, be certain to take all necessary
safety precautions and always work safely..
August
4, 2003
Sponsored
by:
Image
Storage for Any Thermal Imager
With the advent of digital storage
media, nearly every modern thermal imager is
capable of storing images electronically. For
thermal imagers that do not have image storage
capability, there are inexpensive and readily
available solutions.
For thermal imagers having a
video output jack there are two options for image
storage. The first option utilizes a VCR to record
desired imagery. Videotape allows for recording
of moving objects and/or dynamic processes. Videotape
is inexpensive, readily available, and special
equipment is not required for playback. Still
images can be captured from videotape using a
video capture board available for most personal
computers.
The second option utilizes a
digital recorder that accepts a standard video
input. With a digital recorder, single frames
of data may be captured to digital media such
as PC cards. Camcorders having a digital snapshot
camera feature may provide the best solution
of all. Several currently available models allow
a thermographer to record to videotape and/or
to capture still images from the video input.
Additionally, the daylight snapshot feature of
the camera may be used to capture high quality
daylight images.
Once images have been
recorded, they can be directly imported into
a PC for storage or incorporation into written
reports
August
11, 2003
Sponsored
by:
Three
Legs are Better Than None
When it comes to providing a
stable platform for a thermal imager, it’s
hard to beat a tripod. As thermal imagers have
gotten smaller and lighter, many thermographers
have all but forgotten this once requisite accessory
that can help provide better quality data while
reducing stress.
For many PdM applications that
require still images only, using a thermal imager
in a hand held configuration is usually sufficient.
However, for applications that require imaging
from a fixed vantage point over extended periods
of time or where videotaping is desired, a tripod
can be an invaluable accessory. When selecting
a tripod there are several things you should
bear in mind:
1. Be sure to select a tripod
capable of carrying the weight of your imager.
2. Tripods should connect directly
to the imager via a 1/4” x 20 set screw.
Tripods with plastic quick releases should be
avoided as they are subject to wear and can cause
an imager to suddenly fall.
3. Tripods with sturdy hardware
and locking systems are more secure and generally
last longer than inexpensive models.
4. Fluid head tripods are preferable
since they provide smooth motion for videotaping
and are less likely to drop an imager if the
head is left unlocked.
When carrying a tripod
be sure to maintain a safe distance from energized
electrical equipment or moving machinery.
August
18, 2003
Sponsored
by:
IR
Imaging for Check Tank Levels
For many facilities, obtaining
accurate product level information for tanks
and silos is critical for effective inventory
management and safety. Under the right conditions,
a thermal imager can quickly indicate product
levels and serve as a cross reference for calibrating
level indicators.
When product is stored in a
vessel, the density of the product is usually
greater than the head space of air or gas above
the stored product. For stored products that
generate heat, levels may be observed by imaging
the vessel’s exterior and noting the temperature
gradient between head space and product.
For stored products that do
not generate heat, it is possible to rely on
solar loading to create a temperature differential.
Under solar loading conditions, vessels will
usually exhibit cooler temperatures above the
product level during the early to mid morning
hours. As the day progresses, the head space
will exceed product temperature and show as a
warm area above the product. This thermal pattern
may remain for up to several hours after sunset
and reverses once the head space cools to below
stored product temperature.
In general, this application
works best for un-insulated vessels having
a high emittance. For vessels with a low emittance,
it may be possible to modify the surface with
a stripe of high emittance paint.
August
25, 2003
Sponsored
by:
IR
Inspections of Electrical Bus Ducts
Electrical bus ducts are a common
feature found in many commercial and industrial
electrical systems. When used to supplement regular
PM, infrared inspections can help to detect loose
or deteriorated connections that can lead to
costly catastrophic failures.
Electrical bus ducts are used
to distribute low voltage power throughout many
industrial facilities. Modern bus ducts are unitized
structures that contain insulated conductors
within a steel casing. Individual sections of
bus duct, each typically 10 feet long, are joined
with bolted connections at the end of each bus
section. Published industry standards recommend
that bus duct connections be manually tightened
every six months.
Even with regular tightening
of bus duct connections, loose/deteriorated connections
are difficult to detect. With the bus duct under
load, a thermal imager can readily detect the
temperature differentials associated with loose
connections. Properly functioning bus ducts should
exhibit no temperature differential in the vicinity
of bolted connections. Because bus duct conductors
are hidden from direct line of sight, any inexplicable
temperature differentials should be investigated
and corrected immediately. Disconnect switches
and cable connections should be checked for thermal
anomalies as well.
To ensure complete coverage,
bus duct should be inspected from both sides
of the duct along its entire length. Termination
cabinets should also be inspected once the
covers have been removed. Annual or semi annual
infrared inspections performed by certified,
experienced thermographers should be used to
supplement regular bus duct maintenance.
September
1, 2003
Sponsored
by:
IR
Inspections of CMU Walls
Concrete Masonry Unit (CMU)
walls are a common construction detail frequently
used in single –story and low rise commercial
block wall construction. An infrared imager can
be used to quickly perform quality assurance
inspections of reinforcing grout details which
are critical to the strength of finished CMU
walls.
During the construction of CMU
walls, concrete grout is used to fill the cavity
spaces of the blocks in order to provide structural
integrity. Vertical details extending from the
foundation to the top of the wall are usually
placed at regularly spaced intervals along the
length of the wall. Reinforcing grout is also
placed around openings for doors and windows
or in areas where wall extra strength is required.
Because grout details
change the thermal capacitance and conductance
of the wall, temperature differentials will
occur wherever grout details are present. Infrared
inspections may be performed under solar loading,
heat loss, or cooling conditions depending
upon local climate and time of day. Properly
installed grout details will appear as uniformly
cool or warm unbroken lines in the subject
wall areas according to time of day and whether
the inspection is performed from the interior
or exterior of the building.
September
8, 2003
Sponsored
by:
IR
Inspections of Emergency Power Systems
UPS systems and emergency generators
are common defenses for facilities where uninterrupted
electrical power is critical. Performed properly,
IR inspections can help to improve reliability
of emergency power systems.
Most facilities perform IR inspections
of their electrical distribution systems at least
annually as part of a PM program. To help ensure
maximum reliability, regularly-scheduled IR inspections
should also include the emergency power systems
as well. When performing infrared inspections
of emergency systems be sure to:
Inspect all backup generators
while running. Begin inspection at generator
output leads and proceed to generator bus,
breakers, and switchgear.
Include all Automatic and
Manual Transfer Switches. Inspect switches
in both normal and emergency positions.
Inspect UPS system controls,
switchgear, battery cells, battery bus and
wiring. Battery cell temperatures should be
the same between cells with no hotspots on
individual cells.
Have adequate load on the
subject emergency circuits This may be accomplished
with normal facility load or by utilizing a
load bank.
Taking the time to properly
include your emergency power equipment in your
IR inspection program can pay huge dividends
by increasing the likelihood that your backup
equipment won’t leave you in the dark
should the power fail.
September
15, 2003
Sponsored
by:
Focus,
Focus, Focus
Proper image focus is still
one of the most important aspects of performing
an infrared inspection. A clear image not only
allows for optimal problem diagnosis, but it
is also critical to accurate temperature measurement.
Clear focus is not difficult
to achieve if you follow a few simple steps:
1. Get as close as safely
possible to your target
2. Take time to carefully
focus for optimum clarity. This may take some
practice if you have a motorized focus mechanism.
3. Ascertain that your target
is stationary.
4. Only shoot from a stable
platform. If imaging from a motor vehicle,
it may be desirable to shut off the engine
to avoid vibration.
5. Be sure your imager is
steady as you capture the image. Gently push
the store button rather than punching it.
6. If using a handheld imager,
consider using a tripod or monopod to help
stabilize your imager.
Once you’ve stored
an image, recall and check for clarity. If
the results are less than perfect, start over.
In addition to greater accuracy, capturing
clear images makes it easier to convey information
to the end user and/or the person who will
eventually perform corrective actions.
September
22, 2003
Sponsored
by:
Spare
Parts to the Rescue
Seasoned professionals know
the value of spare parts when it comes to facility
maintenance. The principle of always being prepared
can be successfully applied to an infrared inspection
program as well.
Like any electrical or mechanical
device, thermal imaging systems are subject to
wear and tear. Having user-replaceable spare
parts on hand can help prevent unscheduled downtime
for your infrared inspection program. Building
a spare parts inventory is easy if you follow
a few simple steps:
1. Examine your equipment
for parts that are subject to physical wear
such as eyepieces, switch covers or hand/neck
straps.
2. Identify which parts are
fragile and are most likely to break such as
viewfinders or external monitors.
3. Determine which items are
critical to operation such as power/video cables,
batteries, fuses, screws and external hardware.
4. Inventory items which are
easily misplaced such as lens caps and flash
cards.
5. Purchase necessary items
as soon as possible to ensure availability
of specialty or custom parts. For critical
items, be sure to purchase extras.
6. Replace spare parts when
utilized to maintain inventory.
After building your spare
parts inventory, keep mission-critical components
in a safe place or with your imager so that
you will have them when needed.
September
29, 2003
Sponsored
by:
Modifying
a Surface for Temperature Measurement
Unknown emittance values are
often the greatest error source when taking infrared
temperature measurements. This error source can
be eliminated by modifying a target with a material
having a known E value.
Some of the modifying materials
that thermographers commonly use include flat-finish
spray paint, PVC electrical tape, masking tape,
and spray deodorants containing powder.
Prior to modifying any surface:
Make sure that it is safe
to contact the subject equipment.
Obtain permission to modify
the surface from the end user.
Ascertain that the selected
modifying material will not melt, catch fire
or emit toxic fumes when heated.
Once you have determined it
is safe to modify a surface, proceed as follows:
1. Place radiometer at desired
location and distance from target. Aim and
focus.
2. Measure and compensate for Reflected Temperature.
3. Apply a surface modifying material having a known E value on target
making certain that material is in full contact with target and there
are no air pockets. Modifying material should be larger than radiometer’s
spot measurement size for the chosen distance from the target.
4. Enter E value of modifying material into radiometer’s E setting.
5. Measure temperature of modifying material once it has reached thermal
equilibrium with target.
6. For greater accuracy, repeat measurement three times and average
the results.
For more information on
the above technique, refer to the Infraspection
Institute Guideline for Measuring and Compensating
for Reflected Temperature, Emittance and Transmittance available
from Infraspection Institute.
October
6, 2003
Sponsored
by:
Fire
Resistant Clothing
Fire Resistant Clothing is required
Personal Protective Equipment for many who work
in high temperature areas or near energized electrical
equipment. If your job requires the use of FRC,
there are several important things of which you
should be aware.
Not all garments classified
as FRC are created equal. When choosing FRC you
should be aware that:
FRC is not fireproof. It
is designed to protect the wearer from burns
by resisting ignition during brief periods
of high temperature exposure such as electrical
arc flashes.
FRC is manufactured with
different materials and different weights.
Be certain that the chosen material is appropriate
for the task at hand.
FRC effectiveness can be
compromised by age, wear, contamination with
flammable materials and the attachment of name
patches or embroidery. FRC can be permanently
damaged by improper cleaning or laundering.
FRC is only effective when
it is worn properly. It should always be worn
as the outer-most garment. If worn over other
layers clothing, the undergarments should be
made of natural fiber and completely covered
by the FRC.
Before wearing FRC, be
certain to understand its proper application
and limitations and how to use it properly.
As always, remember to work safely!
October
13, 2003
Sponsored
by:
The
Problem with Glass and Plastic
Glass viewing windows and plastic
safety barriers are common features found on
medium and high voltage electrical enclosures
and devices. Although glass and many plastics
are transparent in the visible spectrum, they
are opaque in the infrared spectrum.
Because infrared equipment cannot
accurately see through glass or plastics, infrared
inspections must be conducted with these materials
out of the line of sight of the infrared test
equipment. When plastic barriers are present,
try the following:
Shift your viewing angle
to try to see around or behind the barrier
Have the qualified assistant
temporarily remove the barrier observing proper
safety precautions
If barrier is short and
the subject device is connected to insulated
conductors, image conductors and report any
inexplicable temperature rise.
When safety glass view
ports are encountered in switchgear enclosures,
it will be necessary to have the qualified
assistant open/remove the subject panels. If
this cannot be done due to safety interlocks,
other types of electrical testing should be
performed during regularly-scheduled PM shutdowns.
As always, any obstructed equipment or equipment
not inspected should be noted as such in the
final written report.
October
20, 2003
Sponsored
by:
Know
Your Safety Requirements
When working in a new facility
or plant area for the first time, you may encounter
safety rules that are new or different. It is
always a good idea to review safety requirements
with the project manager prior to project start
to ensure that you are prepared.
When contacting a project representative
concerning safety, be sure to ask the following:
What general safety training
and/or site specific training is required?
Is special clothing, shoes
or other Personal Protective Equipment required?
Can infrared and related
test equipment be used in the subject areas?
Are respirators or additional
safety equipment/monitors required?
Will the work involve hazardous
locations such as confined spaces, scaffolding
or elevated platforms?
What medical conditions
might preclude a person from working in the
subject area(s)?
Are there site specific
emergency procedures including evacuation,
designated rally spots and how to report an
incident?
Once the project commences,
be sure to maintain good situational awareness
and always stay with your qualified assistant.
Becoming familiar with area safety rules in
advance of a project can help to avoid cancelled
projects and embarrassment while helping to
maximize safety.
October
27, 2003
Sponsored
by:
Compensating
for Reflected Temperature
When performing infrared temperature
measurements, reflected infrared energy can be
a significant error source. This potential error
source can be overcome by using the proper radiometer
and test procedure.
All thermographers have experienced
reflected energy when inspecting low emittance
targets. For qualitative imaging, single-point
reflections may be avoided by changing viewing
angle.
With quantitative imaging, failing
to compensate for reflected energy can account
for significant measurement errors. The infrared
energy received by a radiometer is the sum of
emitted, reflected and transmitted energy (E+R+T=1.0).
For targets with a transmittance of zero, the
error sources are emittance and reflectance.
Using a quality radiometer, reflected energy
can be measured and compensated for by using
the Reflector Method described below.
1. Set radiometer Emittance
control to 1.00
2. Locate radiometer at desired distance from target to be measured
3. Aim and focus imager
4. Position diffuse reflector in front of, and parallel to, face of
target
5. Measure apparent temperature of reflector surface and remove reflector
6. Enter value obtained in Step 5 into radiometer’s computer
under reflectance input – commonly labelled Background, TAmbient,
or Reflected Temperature.
Be sure to maintain a safe working
distance from any energized or potentially dangerous
targets. For more information on this subject,
refer to Infraspection Institute’s Guideline
for Measuring and Compensating for Reflected
Temperature, Emittance & Transmittance.
November
3, 2003
Sponsored
by:
Using
a First Surface Mirror
Proper conduct of an infrared
inspection requires line of sight access to the
object(s) being inspected. A first surface mirror
can often be utilized to inspect components that
may be obstructed or obscured.
A first surface mirror is a
special optical mirror that has a highly reflective
coating adhered to the front of the mirror substrate.
For infrared inspections, first surface mirrors
can be temporarily utilized as reflectors to
inspect areas that are inaccessible or unsafe
for a thermographer to enter.
When using a first surface mirror
with your infrared imager, keep the following
in mind:
Select a mirror of sufficient
size for the selected imager and target
Inspect mirror prior to
use for cleanliness and condition
Place the mirror in the
optical path between the imager and object
being inspected
Position the mirror so that
the reflective side of the mirror faces the
imager
Inspect object by imaging
mirror surface
First surface mirrors
are commercially available from a number of
scientific suppliers that deal with optics
and lasers. When using a first surface mirror,
be certain to follow necessary safety precautions,
especially when working near energized electrical
components.
November
10, 2003
Sponsored
by:
Outsourcing
IR Services
Whether you are considering
instituting an IR inspection program or already
have one in place, obtaining competent manpower
can be a challenge. One potential solution is
to outsource services for additional manpower
and expertise.
There are many factors that
will determine if a person is capable of effectively
supporting your infrared program. Your success
in qualifying your thermographers can be increased
if you keep the following in items in mind when
qualifying individual thermographers.
Proof of formal infrared
training and certification level
Amount of experience with
the type(s) of inspections planned
Experience with the selected
test equipment
Knowledge of the system(s)
being inspected
Documentation of requisite
safety training
If you choose to outsource your
thermographers through an infrared consulting
firm, you may also wish to check the following.
Number of years in business
Type of infrared equipment
to be utilized and calibration dates
Insurance coverage
Safety records and experience
modification rating
Professional references
Depending upon your company
requirements, be sure the chosen vendor is
capable of complying with security, background
screening, and substance abuse policy requirements.
November
17, 2003
Sponsored
by:
Autumn
is the Time for Steam Trap Testing
With the onset of seasonably
cooler weather, autumn is the time to prepare
your steam system for the upcoming heating season.
Testing your steam traps before the season begins
can help to pinpoint costly leaks before the
heating season begins.
Traditionally, two different
non-destructive technologies have been employed
to test steam systems – contact ultrasonics
and temperature measurement. Used individually,
each of these techniques has limitations that
can lead to false positive and/or false negative
results. Combining temperature measurement with
ultrasound can result in a highly accurate test
method by following a few simple steps:
Measure trap inlet
to ensure that temperature is above 212º F
If trap inlet is below
212º F, ascertain why steam is not
reaching trap
Listen to the trap
outlet with contact probe of ultrasonic unit
Continuous hissing
or rushing sounds usually indicate a
failed trap
Ascertain that trap
is cycling periodically
Frequent cycling may
be caused by an undersized or worn trap
Tag defective traps and
document in written report
Re-test defective traps
after repair to ensure effectiveness of repair.
Always be sure to follow
appropriate safety precautions especially when
working with high pressure steam or when using
ladders or lift equipment.
November
24, 2003
Sponsored
by:
Do
You Have the Correct Time?
Most modern thermal imagers
have the ability to record time and date along
with thermal images. Taking a moment to ensure
that the correct time and date are displayed
on your imager before you begin your inspection
can help to avoid wasted time and the collection
of inaccurate data.
Having the correct time associated
with your imagery is important for several reasons.
With correctly dated imagery, it is possible
to:
Accurately document when
the inspection was performed
Easily store and uniquely
reference image files
Record the duration of a
thermal event
It is always good practice to
consciously check your imager’s clock each
time you start your imager and make any necessary
adjustments. Be certain to check your clock periodically
during your inspection and whenever you restart
your imager such as after a battery change or
power interruption.
If your imager frequently
displays incorrect time, it may be indicative
of a defective or dead internal battery. To
help avoid this problem, arrange for replacement
of internal clock batteries whenever you have
your imager serviced or repaired.
December
8, 2003
Sponsored
by:
Splash
Protection for Your IR Imager
Taking your infrared imager
into dusty or wet environments can have disastrous
consequences for your imager. While it is best
to wait for such conditions to subside, your
can use a polyethylene sheet or trash bag to
temporarily protect your imager and accomplish
a qualitative inspection.
Since not all imagers and trash
bags are created equal, you can follow the following
steps to ensure good results.
1. Set up imager looking at
thermally stable target with a high emittance.
If using an imaging radiometer, note the apparent
temperature of the target.
2. Select a clean, unused, polyethylene trash bag with a uniform thickness.
3. Open trash bag and place over imager. Use only a single layer of
the bag plastic to cover the lens.
4. Use a rubber band to keep plastic smooth and wrinkle free over the
imager lens.
5. Image target in Step 1 again and note image quality and apparent
temperature.
6. Repeat above steps using different brand bags and thicknesses until
you find a bag that gives minimal attenuation of image and apparent
temperature.
7. After selecting the bag that works, trim to fit imager so as to
prevent a tripping hazard. If your imager requires air cooling, leave
the bottom of the bag open so the imager can ‘breathe’.
8. When finished imaging, remove bag from imager and discard.
While not glamorous, this
procedure can allow you to successfully perform
a qualitative inspection in an environment
that might otherwise harm your imager.
December
15, 2003
Sponsored
by:
Renting
a Thermal Imager
Whether you are facing an equipment
shortage or looking to evaluate the characteristics
of a new imager prior to purchase, renting a
thermal imager may provide a solution. As with
purchasing an imager, there are several important
things to consider when arranging for a rental
unit.
To help ensure that you select
an appropriate imager for rental, be certain
to:
· Identify appropriate
spectral response required for project
· Determine if temperature
measurement is required
· Evaluate the system
for objective specifications
· Ascertain imager
compatibility with reporting software
When arranging for a rental,
obtain terms and conditions from the rental agency.
These should include, but not be limited to:
rental period, extension of rental, shipping
costs, and requirements for insurance against
loss. One should also consider the rental agency’s
ability to provide technical support during the
rental period.
For more information on specifying
an infrared imager, refer to the article, “Selecting,
Specifying, and Purchasing a Thermal Imager” which
may be found on this website here.
Lastly, the greatest limiting
factor in any infrared inspection is the thermographer.
For accurate results, infrared inspections
should be performed by properly trained and
certified thermographers. For more information
on training, please contact Infraspection Institute.
December
22, 2003
Sponsored
by:
Our
Most Important Tip
With the end of the year upon
us, we wish to follow in the grand tradition
of saving our best for last. In this Tip of the
Week, we address some of the most important issues
facing predictive maintenance professionals.
With the holiday season in full
swing, we invite PdM technologists and thermographers
throughout the world to consider the issues of
inventory, reliability and communication and
offer our best advice as follows:
Inventory – Take time
to reflect on your many blessings such as good
health, family and friends.
Reliability – Set
time aside to appreciate having friends and
relatives in whom you can confide and trust.
Communication – Remember
to share your feelings with all of the special
people in your life by letting them know what
they mean to you.
Spreading cheer and holiday
spirit is easy; it begins with each of us as
we let others know how we feel about them.
As we enjoy this holiday season,
we extend a heartfelt Thank You to all of our
readers, friends, and associates throughout the
world for everything that you do for us all year
long.
May your holidays be filled
with peace and joy and your New Year with good
health and happiness.
~ Jim & Chris Seffrin
December
29, 2003
Sponsored
by:
Thermography
and NFPA 70B 2002 Edition
For the past decade, the document,
NFPA 70B Recommended Practice for Electrical
Equipment Maintenance, has recommended annual
infrared inspections of electrical systems. The
2002 edition of NFPA 70B contains several revisions
of which thermographers should be aware.
The 1994 edition of NFPA 70B
outlined many important issues surrounding infrared
inspections including training, equipment, required
conditions, inspection frequency, and reporting.
The 1998 edition expanded on these issues and
referenced temperature limit benchmarks. The
2002 edition text is nearly identical to the
1998 edition for the chapter, “Infrared
Inspections”; however, there are some important
changes:
Specifications for Infrared
Inspections have been moved from Chapter 18-17
to
Chapter 20.17
Chapter 20.17.52 is a new
addition, requiring that circuit loading characteristics
be included as part of report documentation
The 2002 edition also contains
a completely revised Annex I recommending infrared
scanning at least once per year for the following
equipment:
Outdoor Substations
Switchgear Assemblies
Stationary Batteries and
Chargers
Motor Control Equipment
Low Voltage Busway
UPS Systems
As with previous editions,
NFPA continues to recommend semi-annual or
quarterly infrared inspections for equipment “…where
warranted by loss experience, installation
of new electrical equipment, or changes in
environmental, operational, or load conditions.”