|
Case Study of a Hotel Missing
Insulation
|
|
|

Tom Mayfield |
|
|
Abstract
The management at a brand-new,
four-star Texas hotel received so many complaints about
the noise from adjoining rooms that they hired an acoustical
engineer to find the problem. The engineer was able to tell
them that they had a problem with missing insulation, but
could not determine where the insulation was missing.
Our firm was hired to locate the areas
where insulation was missing so that repairs could be made
under warranty by the general contractor. This paper describes
the methodology developed and shows the results of that
testing.
Discussion
The Problem
A four-star Texas hotel opens its doors to
the public. The customers quickly respond to noise problems
from room to room...after all, who wants to pay $200+ for
a nice room and then have to share your conversations with
the neighbors as if they were in your room. After four months
of noise complaints, the management decided an investigation
needed to be launched to solve the problem.
At that point, the hotel contacted
an acoustical engineer to perform some STC (Sound Transmission
Class) testing. STC is a single number quantifier used to
rate partitions, doors and windows for their effectiveness
in blocking sound. This whole process is based on a standardized
procedure defined in ASTM E90 for laboratories and E336 for
field tests in actual buildings; while the STC curve is defined
in ASTM E413. In practice, the STC of the laboratory sample
represents the optimum condition and is rarely achieved in
actual construction. The difference between the actual and
field STC is a result of leaks and flanking paths. In other
words, sound entering a wall in a common assembly is also
entering the floor, traveling through the floor, and breaking
out in the adjoining space, therefore by-passing the wall.
A similar effect is found if sound is allowed to enter air
return plenum spaces above, below, or through the walls. The
degree to which these flanking paths are disconnected will
determine how closely the field test results approach the
laboratory results. Table 1, below, defines the various STC
levels that acoustical engineers use.
| STC Lab |
STC Field |
Subjective Description of Effectiveness |
| |
|
|
| 26-30 |
20-22 |
Most sentences clearly understood |
| 30-35 |
25-27 |
Many phrases and some sentences
understood without straining to hear |
| 35-40 |
30-32 |
Individual words and occasional phrases clearly heard
and understood |
| 42-45 |
42-45 |
Medium loud speech clearly audible,
occasional words understood |
| 47-50 |
40-42 |
Loud speech audible, music easily heard |
| 52-55 |
45-47 |
Loud speech audible by straining to hear; music normally
can be heard and may be disturbing |
| 57-60 |
50-52 |
Loud speech essentially inaudible;
music can be heard faintly but bass notes disturbing |
| 62-65 |
55 |
Music heard faintly, bass notes "thump"; power
woodworking equipment clearly audible |
| 70 |
60 |
Music still heard very faintly if played loud |
| 75+ |
65+ |
Effectively blocks most airborne noise sources |
| |
|
|
| Table 1. Subjective
interpretation of effects of STC as measured (assumes
normal/quiet background level - NC 35) |
Notes for Table 1:
• The level noted in Red
is the approximate level causing noise complaints at this
hotel
• The level noted in Blue
is the normal/quiet background level of STC 35
• The level noted in Green
is the required STC 50 level for current building construction
• Changes in the National Building
Code 1990 now require that partitions separating dwelling
units meet an STC 50 requirement and the building code provides
sample ratings for several types of wall constructions
The acoustical engineer could quantify
that there were indeed major problems, but could not point
to the exact locations causing the problems. Fortunately,
the acoustical engineer knew about infrared thermography and
knew about my company, so he suggested that the hotel contract
us to perform a feasibility study to see if infrared could
define and quantify the problems. The thermogram below (Figure
1) represents what we found in the first room that we surveyed.
After they saw the results of the feasibility study, they
decided infrared thermography was THE way to quantify the
missing insulation problems.

Figure 1. Thermogram
showing missing insulation
The IR Project
How do you infrared survey 1600 guest
rooms in a hotel in full operation with an occupancy rate
between 30% and 100% with an average occupancy rate around
80%? The obvious answer is one room at a time, but the hotel
wanted a plan. We first attempted to deal with the many rooms
that had the most noise complaints, but they were spread out
and we needed at least three contiguous rooms at the same
time; the noisy room, and the rooms on either side (more about
this below). As it turns out, this was inefficient as we found
ourselves bouncing around the hotel like ping pong balls,
walking 5-8 miles a day, instead of IR surveying. My suggestion
was to wait instead of walk. We waited for those times when
their occupancy rate was 50% or lower and then took 100 or
more rooms out of service at once in one area and on one floor.
We would go in 24 hours before the IR survey and heat every
other room, so that the result was alternating hot and cold
rooms (hot – cold – hot – cold). That way,
the adjacent rooms always had a 15-20 degree Delta-T in ambient
temperature. As we proceeded, anomalies were documented and
reports were generated on the rooms surveyed during each session.
The data collection was accomplished with an assistant who
entered the textual data as the thermographer dictated the
findings one wall at a time. We established a set procedure
for scanning (always left to right) and a set procedure for
data entry (see Table 2). We also used the same terminology
to identify each of the walls and objects in each room. To
lessen confusion and always make the anomalies colder than
the rest of the wall, the polarity was reversed if necessary.

Table 2. Spreadsheet
of example data contained in thermographic reports
Click
here to enlarge the spreadsheet above

By the time we finished scanning a section
of rooms, the report text was basically complete. To prepare
the reports, all we had to do was proofread the text and do
the image post-processing, which consisted of adjusting the
brightness and contrast and inserting each thermogram into
the appropriate spot on the report page. By converting the
file into a secure PDF, only printing could be performed on
the document once we turned in the report.
The Results
The rooms averaged a failure rate of 85%,
meaning 85% of the rooms surveyed had at least one problem
requiring repair (see Figures 2, 3, 4, & 5). The problems
ranged from missing insulation to moisture issues (mostly
from overflowing bath tubs) and a few condensation problems.

Figure 3. Thermogram
showing missing insulation in partition wall

Figure 4. Raw thermogram
showing installation of a 16” batt (yellow arrow)
in a 24” stud space (white arrow)

Figure 5. Thermogram
showing evidence of an uninsulated pipe chase on a bathroom
wall.
Inset is a photograph taken after IR testing
The Fix
The GC was definitely responsible for not
meeting the specifications and for making the repairs. The
hotel had proof positive of the deficiencies, and because
all the walls were documented, they knew exactly where the
repairs had to be made. After each report was submitted, the
general contractor was required to schedule complete repairs
on the same block of rooms which were taken out of service
for the IR testing. This was a two day process for each room
as they would remove the sheetrock, replace the missing insulation,
and repair the sheetrock on the first day. On the second day,
they would finish the sheetrock, and paint or wallpaper the
repaired areas. In order to help the acoustical issues, the
repairmen also air-sealed the rooms during this process. They
were only able to accomplish this for 100 or 200 rooms at
a time owing to large repair crews of between 50 and 100 workers.
Summary
This was a very successful project
and an example of how well IR can work as a quality-assurance
tool for buildings.
|