|
|
Using Infrared Sightglasses to
Protect Against Arc-Flash Exposure |
|
|

Paul Campbell,
Presenter |
|
|
Abstract
This paper explores the applicable
standards currently in place in industry and assesses their
impact on infrared sightglass and port design, implementation
and corresponding safety in use.
Introduction
The intense energy and duration
of an electric arc-flash represents a very unique exposure.
Everyday work clothes made from regular cotton or polyester-cotton
blended fabrics, regardless of weight, can be readily ignited
at some exposure level. Once ignited, the clothing will continue
to burn, adding to the extent of the injury sustained from
the arc alone. The National Fire Protection Association (NFPA),
“Standard for Electrical Safety Requirements for Employee
Workplaces”, now requires employees to wear flame resistant
(FR) protective clothing wherever there is possible exposure
to an electric arc-flash. This clothing must meet the requirements
of ASTM International, formally known as the American Society
for Testing and Materials (ASTM), document reference F1506.
It also requires employers to perform a flash hazard analysis
to determine the flash protection boundary distance.
Discussion
NFPA 70E is the standard for the protection
of employees working inside various flash protection boundaries.
It specifies a level of protective clothing for the corresponding
Hazard/Risk Category. The rating of the clothing must have
an ATPV of at least the value listed in the "Protective
Clothing Characteristics" section of the standard. The
Occupational Safety and Health Administration (OSHA) has confirmed
that garments which meet the requirements of ASTM F1506 are
in compliance with OSHA 29 CFR 1910.269: Electrical Power
Generation, Transmission and Distribution.
Infrared Viewing
Systems for Electrical Equipment
Infrared scanning must be performed with
the target equipment energized. Infrared cameras cannot “see”
through panel covers. Consequently, thermographers face severe
safety hazards when attempting to scan electrical distribution
equipment. The installation of infrared sightglasses (windows
or ports) is an excellent solution to this predicament. However,
special care must be taken to ensure that the construction
of the sightglass does not put the thermographer or the equipment
at risk. As IR sightglasses are a new and emerging technology,
there are no specific standards that relate to approved sightglass
construction and testing. This has lead to potentially dangerous
materials being incorporated into some IR sightglass assemblies.
As user requirements for IR sightglasses
vary from some of the more traditional switchgear type applications,
testing and certification needs to be generic. This ensures
that the product will be suitable for general purpose applications.
“Viewing
Pane” Standards, IEEE C37.20.2 A3.6
15kV Metalclad
Switchgear
to IEEE C37.20.21 |
 |
Fig 1. IEEE C37.20.2 compliant
cabinet
|
Figure 1 illustrates a medium voltage disconnect
manufactured by a major OEM in accordance with IEEE C37.20.2.
This example clearly shows both viewing panes for any time
visual inspection and also IR sightglasses for periodic infrared
inspection, highlighted A & B respectively.
There are some obvious differences between
the two inspection points:
a) The infrared inspection windows labeled
with ‘B’ include locking security covers which
require a trained and authorized person to remove before attempting
an IR scan. This should be deemed a necessity on all such
products in order to protect the optic material from day-to-day
impacts. The cover provides an additional level of protection
under arc-flash conditions.
b) In stark contrast, the viewing windows
labeled ‘A’ are only designed to withstand accidental
impact and only to provide basic visual observation. They
are not designed to withstand the combined pressure piling
and sudden temperature increase resulting from an internal
electric arc.
The C37.20.2 standard incorporates a specific
section referred to as “viewing panes” which dictates
testing requirements for impact and pressure for visual inspection
devices.
The following is excerpted from section A.3.6
of the standard titled “Viewing Panes” and specifies
the following:
“A transparent material covering
an observation opening and forming a part of the enclosure
should be reliably secured in such a manner that it cannot
be readily displaced in service and should meet the following
requirements:
a) Viewing panes should not shatter,
crack, or become dislodged when both sides of the viewing
panes in turn are subjected to the tests described below.
b) A force of 445 N (100 lbf) should
be exerted perpendicular to the surface in which the viewing
pane is mounted. This force should be distributed evenly
over an area of 0.010 m2 (16 in2) (as nearly square as possible
and as near the geometric center of the viewing pane as
possible). If the viewing pane has an area less than 0.010
m2 (16 in2), the force should be evenly distributed over
the entire viewing area. The 445 N (100 lbf) should be sustained
for a period of 1 min.
c) The viewing pane should be subjected
to an impact of 3.4 J (2.5 ft-lbf) using a steel ball weighing
approximately 0.54 kg (1.18 lb) and measuring approximately
50 mm (2 in.) in diameter.
d) Separate samples may be used for
each of the tests described in a), b), and c).
e) If a viewing pane is intended to
be exposed to insulating oil in a tank or compartment, it
should be made of a material that is resistant to the corrosive
effects of the insulating oil.
f) Category A equipment should have
lockable covers over viewing panes if viewing panes are
furnished.”
It is important to understand that
the intent of this section of the standard is to properly
evaluate its importance and potential effect on an IR sightglass;
IEEE C37.20.2 is not in any way an arc-resistant switchgear
standard and hence its impact on products designed for installation
into this end-use requirement, i.e., arc-flash risk and injury
mitigation do not apply. This is in contrast to IEC 62271-100
for example, which clearly defines the criteria for arc-resistant
equipment and testing.
The Annex A3.6 section of C37.20.2 was written
for a non arc-resistant viewing pane. The main function of
the pane or window is to provide the operator with a means
to visually confirm the state or position of an interrupt
device. Very few arc-resistant panels incorporate viewing
panes and those that do usually utilize a protective cover
or have been tested to comply to current arc resistant testing
standards.
As the viewing pane is constantly exposed
and subject to possible day-to-day impacts associated with
normal day-to-day use in any industrial location, impact testing
on any “optic” is a requirement.
Some infrared sightglasses utilizing crystal
optic materials are designed to protect the infrared thermographer
performing scheduled, periodic inspection of the internal
equipment, even under arc-flash conditions.
Invariably, these types of designs incorporate
a protective security cover which is in place to absorb these
day-to-day accidental impacts. Properly constructed cover
designs are manufactured from materials such as aluminum,
which offer substantially similar properties to those of a
panel wall knock-out referred to in the National Electric
Code 110.12(A).
Such protective covers are generally
secured to the mounting ring using a locking mechanism which
limits access to the “optic” to authorized personnel.
These people should be trained to understand the level of
risk reduction provided and take appropriate precautions when
making use of the device.
IEEE C37.20.2
and IR Port Implementation
 |
Fig 2. Typical locking security
cover
|
The C37.20.2 standard also incorporates a
specific section relating to “Enclosure Openings”
which must be taken into account if IR ports are being considered.
Paragraph A.3.3.1 “Enclosure Openings”,
describes the minimum requirement for an opening in an enclosure.
It should be noted that the “Enclosure Openings”
and “Ventilation Openings” are referred to separately.
IR ports perform the same basic function
as IR sightglasses except that the transmitting “medium”
is a mesh, grill or open hole which allows infrared radiation
to pass through. Obviously, such devices provide virtually
no protection to the thermographer or operator in the event
of an arc-flash event. In some equipment configurations where
ventilation grills are required, they may be considered for
use.
 |
Fig 3. Dedicated lens/port
arrangements
|
Figs. 2, 3 and 4 show a variety of infrared
port designs, ranging from a mesh/grill option, which may
be used with any infrared camera to a dedicated port and “fish-eye”
type lens arrangement.
 |
 |
| Fig 4. Universal IR port and warning labeling |
Fig 5. Internal mesh screen
for IR scanning
|
A screen barrier
such as that shown in Fig. 5 provides excellent coverage to
internal components but requires outer cover removal to complete
the scan.
When utilizing such products, it must be
clearly understood that the primary design and installation
parameter is the diameter of the opening. The C37.20.2 standard,
section A3.3.1, details the maximum enclosure opening, excluding
ventilation openings, being no greater than 13mm (0.5”).
The European Standard EN60529 incorporates a similar requirement,
referred to as IP2X. IP2X defines protection against fingers
or other objects not greater than 80mm in length and 12mm
in diameter.
Fig. 6 shows the definition of the IP2X convention
known as “fingerproof”. The rationale is to prevent
a foreign object, the size of a human finger, from penetrating
the equipment and coming into contact with live components.
The size of the opening and its environmental
location (indoor or outdoor) must be seriously considered
before installing an IR port. In order to install an IR port
with an opening greater than 0.125” but less than the
maximum 0.5” as required by C37.20.2 A3.3.1, certain
clearances must be adhered to. Table 1 outlines these requirements.
| Table 1 |
| |
|
Rated Maximum
Voltage in kV |
Clearance |
in. |
cm. |
| 4.76 |
5.5 |
14 |
| 8.25 |
6.5 |
17 |
| 15.0 |
8.0 |
20 |
| 27.0 |
12.0 |
30 |
| 38.0 |
15.0 |
38 |
For example: If the end use requirement is
on a 15kV circuit breaker structure and the distance between
the proposed IR port installation and the nearest un-insulated
live part is less than 8” (20 cm) then the maximum opening
or “hole” in the IR port or screen must be less
than 0.125” (3.2mm).
The National Electric
Code – NFPA 70 (NEC)
Unlike IEEE C37.20.20, which is specific
to non arc-resistant metal-clad switchgear, the NEC is a generic
standard relating to electrical equipment, both domestic and
industrial. The most recent iteration of the NEC is the 2005
edition which was approved as an American National Standard
on August 5, 2004.
The 2005 edition of the NEC includes for
the first time a reference to “Flash Protection”.
NEC paragraph 110.16 recognizing that switchgear, panelboards,
industrial control panels, meter socket enclosures and motor
control centers are to be field marked to warn users of a
potential flash hazard. This is an important step forward
in the codes, recognizing the increased awareness associated
with arc-flash hazards and their impact on the maintenance
and operation of electrical equipment.
The code includes a number of paragraphs
that apply to the design and implementation of IR sightglasses
and ports, with flash protection being the primary point.
As outlined earlier, although crystal optics
used in some IR sightglasses can be designed to withstand
the effects of pressure piling and temperatures associated
with an arc-flash event, the optic cannot withstand day-to-day
point impacts caused by careless personnel or the general
public. To overcome this relatively minor problem, IR sightglasses
are generally supplied with a locking protective cover as
standard (Figs. 2 & 4). NEC section 110.31(D) confirms
the requirement for such covers and guards to protect such
openings.
Basic material recommendations for construction
of electrical equipment are also covered in NEC 2005. Infrared
sightglasses have a variety of possible areas of installation,
including equipment such as transformers and motors and, as
such, the construction material of the mounting ring and protective
cover should also be considered.
Switchgear, motors, transformers, etc. are
almost exclusively manufactured from metal and this same material
has been the choice for IR sightglass manufacturers. IR sightglass
installations into such areas as motor terminal boxes and
switchgear structures require a similar level of protection
as provided by the original material. NEC requires that motor
terminal boxes be made from metal and be of substantial construction
- the same should apply to an IR sightglass.
NEC section 490.40 also refers to “Inspection
Windows” in that they simply require the optic to be
of a suitable transparent material and require that cover
plates be installed on openings to provide adequate protection
when the opening is not in use.
IEC 62271-200
Arc-Resistant Switchgear
Perhaps the best overall standard applicable
to IR windows for end-use application into arc-resistant switchgear
is IEC62271-200, published in 2003. 62271-200 covers AC metal-enclosed
switchgear and control gear for rated voltages above 1kV and
up to and including 52kV and refers to standards such as IEEE
C37.20.7:2001 as a guide for testing MV metal-enclosed switchgear
for internal arcing faults.
Plastic materials used in the construction
of a sightglass are obviously not acceptable for use on equipment
whose end-use function is to prevent injury in the event of
an electric arc. With respect to IR sightglasses, 62271-200
requires that covers and doors that are part of the enclosure
shall also be metallic. Fig. 2 gives an example of an IR sightglass
with a metallic cover.
IEC 62271-200, paragraph 5.102.4 - “Inspection
Windows”, defines the requirements for inspection windows
designed for installation into 1kV to 52kV arc-resistant equipment.
 |
Fig 7. Results of an arc-fault
test including
IR sightglass installation
|
In accordance with this section, infrared
sightglasses should:
a) Provide at least the degree of protection
specified for the enclosure
b) Be covered by a transparent sheet with
a mechanical strength comparable to that of the enclosure
Point a) refers to the environmental protection
of the enclosure defined by EN60529 in Europe or by NEMA/UL50
in North America and requires that the sightglass installation
does not de-rate the enclosure.
Point b) refers to the strength of the optic
itself. If the optic material can pass all testing in accordance
with paragraph A.6 “Acceptable Criteria”, then
it can be deemed acceptable as a part of an IAC piece of equipment.
Fig. 7 illustrates the typical result of
a 20kA arc-flash test in accordance with IEC62271-200 on a
12kV VCB with an IR sightglass installed.
The damage shown in Fig. 7 is the result
of the dynamic pressure wave rather than the build-up of static
pressure within the enclosure. In fact, as a result of this
damage and corresponding pressure “relief”, the
actual static pressure increase within the enclosure was minimal
and extremely short lived.
This poses an interesting question when testing
an IR sightglass for suitability of installation into equipment.
Where there is the possibility of an arc-flash event, is static
pressure testing enough or should a “dynamic”
or thermoacoustic pressure test be required?
Although in this instance the IR sightglass
optic shattered, it was deemed a result of the host equipment
buckling rather than destruction due to the thermoacoustic
pressure wave. As the cover and entire assembly remained attached
to the panel and no material or arc gases were ejected, the
IR sightglass passed the test in accordance with the acceptable
criteria shown in Annex A of IEC 62271-200.
Melt Fabrics and
Polymer Optics
Recently, lower cost IR windows have been
introduced into the industry. Rather than using the traditional
crystal-type optic, these products use a disc of a thin polymer
material as the transmitting medium.
 |
Fig 8. UL 746C type burn test
results
on polymer optics
|
It is important to note that so called “melt-fabrics”
are specifically prohibited by the standard for use with any
FR PPE. This requirement obviously covers faceshields and
as such, should also apply to infrared sightglass optics/lenses
which are directly between the operator and the arc-flash.
“(a) Melting. Clothing made from
flammable synthetic materials that melt at temperatures
below 315°C (600F), such as acetate, nylon, polyester,
polypropylene, and spandex, either alone or in blends, shall
not be used.” NFPA70E 130.7(14)(a).
Such fabrics may cause severe contact/melt
burns under a fault condition, even though basic impact resistance
of such materials is good. The sudden increase in temperature
and pressure associated with an arc flash, causes the optic
to change into what is ultimately a molten projectile.
Fig. 8 shows the effect of a UL 746C
type burn test on a polymer optic IR window. It is clear that
in order for the “optic” to be infrared transmissive,
its thickness must be such that it has no thermal endurance.
In fact, testing shows that such materials melt at temperatures
less than 100°C, far less than the 315°C required
by NFPA 70E for synthetic PPE. Even if such materials are
backed onto supporting mesh, the polymer optic will fail in
the same manner causing a dangerous scenario, potentially
involving a molten polymer projectile.
Since OSHA 29 CFR 1910.269 prohibits garments
which contribute to burn severity, it is the author’s
opinion that such thin film polymer optics, even mesh reinforced
options that can literally comply with basic impact tests
such as IEEE C37.20.2 A3.6, cannot be used in equipment with
the capability to sustain an electric arc. Such products must
be limited to <50V control equipment that, due to electrical
or mechanical interlock devices, prevents door or cover removal
and has no requirement for a high strength arc resistant crystal
optic.
It is important to be clear as to the reason
for installing IR sightglasses and for the philosophy behind
the present switchgear and electrical equipment standards.
As discussed earlier in this paper, the primary driving force
behind the installation of infrared sightglasses is NFPA 70E
as a method for reducing arc-flash danger and injury.
In fact, in response to an inquiry on OSHA's
stand on arc-flash hazard, Richard S. Terrili, the Regional
Administrator for Occupational Safety and Health, US Department
of Labor for the Northwest Region at Seattle, concluded as
follows:
"Though OSHA does not, per se,
enforce the NFPA standard, 2000 Edition, OSHA considers
the NFPA standard a recognized industry practice. The employer
is required to conduct assessment in accordance with CFR
1910.132(d)(1). If an arc-flash hazard is present, or likely
to be present, then the employer must select and require
employees to use the protective apparel. Employers who conduct
the hazard/risk assessment, and select and require their
employees to use protective clothing and other PPE appropriate
for the task, as stated in the NFPA 70E standard, 2000 Edition,
are deemed in compliance with the Hazard Assessment and
Equipment Selection OSHA standard."
NFPA 70E requires that employees wear appropriate
flame resistant (FR) protective clothing if performing “live”
work within the arc-flash boundary. The closest equivalent
to an IR sightglass contained within NFPA 70E is the faceshield.
Both being transparent; one being optical and one being an
infrared.
Article 130 Table 130.7(C)(8) dictates
how to properly test and assess face protective products such
that they hold an “Arc Rating” which can be incorporated
into an FR PPE configuration in accordance with article 130.7(C)(13)(b).
This rating is quantified in cal/cm2. Table 2 illustrates
how to relate this rating into a hazard/risk category such
that appropriate options can be selected.
| Table |
PPE Selection
Table |
| |
|
| Hazard/Risk Category |
CLOTHING DESCRIPTION
(Typical number of clothing layers
is given in parentheses)
|
Required minimum
Arc-Rating of PPE (cal/cm2) |
| 0 |
Non-melting, flammable
materials 4.5 oz. (1) |
N/A |
| 1 |
FR shirt and FR pants
(1) |
4 |
| 2 |
Cotton underwear,
plus FR shirt and FR pants (2) |
8 |
| 3 |
Cotton underwear,
plus FR shirt and FR pants, plus FR coverall (3) |
25 |
| 4 |
Cotton underwear, plus FR shirt and FR
pants, plus double-layer switching coat and pants (4) |
40 |
Using this methodology, it is now possible
to provide a meaningful arc rating of an IR sightglass that
is applicable to different equipment at different voltages
but can be considered “generic”.
Assessing the Risks
Associate with IR Sightglasses
Ultimately, the installation of IR sightglasses,
as with the use of any PPE, is a method to reduce the risk
associated with a specific task.
The definition of “risk” is “the
possibility of loss or injury”. The installation of
an IR sightglass certainly helps in reduction, however, we
must utilize the different optic options available in the
most suitable end-use requirements in order to properly quantify
“risk”.
Since arc-flash radiant energy is not solely
voltage dependant, it is not correct to place a voltage related
restriction on the selection of IR sightglass optics. The
exception is under circumstances where the voltage level is
insufficient to strike and/or maintain an arc.
Appendix 1 shows a selection matrix
detailing how to correctly select a minimum IR sightglass
optic material based upon arc-flash protection end-use requirements
and host equipment specifications.
Testing Methods
for Infrared Sightglass Optics and Mountings
As a minimum, IR sightglasses should be tested
for their ability to withstand typical end-use forces which
have been demonstrated as arc-flash effect.
In relation to IR sightglasses, there are
three primary effects of an electric arc-flash that must be
considered and tested in order for the sightglass to be suitable
for use and be a true risk reduction and injury mitigation
tool. They are:
• Static internal pressure increase
• Dynamic “thermoacoustic”
wave effects
• Heat-flux effects
Each point will be discussed in turn, with
a conclusion as to acceptable test criteria.
Static Pressure Effects
The static pressure within a cubicle is basically
a function of the internal volume. This can be expressed by
the Ideal Gas Law.
For the purpose of calculations, it
is convenient to place the Ideal Gas Law in the form:

where the subscripts i and f refer to the
initial and final states of some process. If the temperature
is constrained to be constant, this becomes:

which is referred to as Boyle's Law.
If the pressure is constant, then the Ideal
Gas Law takes the form:

which has been historically called Charles'
Law. It is appropriate for experiments performed in the
presence of a constant atmospheric pressure.
All the possible states of an ideal gas can
be represented by a pVT surface as illustrated in Fig. 9.
The behavior when any one of the three state variables is
held constant is also shown.
As described in the earlier example,
static pressure testing only represents one of the effects
of an arc fault. By combining all three test variables represented
in this section, we can get an accurate representation of
the optic strength under a pVT effect which includes a thermoacoustic
wavefront.
The simple relationship between pressure
and volume can be derived as:

Graphically, this can be represented by Fig.
10, below:
 |
Fig 10. Volume / Pressure
relationship
|
It is important to note that Volume is not
equivalent to Area and as such, the general equation P = F/A
does not apply.
During an electrical arc-flash event, the
static pressure within an enclosure increases until either:
a) A pre-designed pressure relief system,
such as a vent, operates (Figs. 13 & 14)
b) Physical disintegration of the system
causes pressure relief (Fig. 7)
Fig. 11 shows an example of a pressure relief
system. Various iterations of this design type are now incorporated
into what is known as arc-resistant control equipment.
 |
Fig 11. Pressure relief plate
|
 |
Fig
12. Pressure increase within
an enclosure during an arc-flash event
|
The pressure relief system operates as a
result of the thermoacoustic wave discussed in the next section.
It does not operate due to the static pressure build-up. As
a result, the internal static pressure reduces.
Fig. 12 denotes the pressure build-up and
release as a function of time inside an arc-resistant piece
of switchgear. The maximum pressure measured was approximately
19 psi.
Fig. 12 clearly shows the increase in pressure
associated with an arc-flash and the resultant drop in pressure
due to the operation of the relief system.
In order to correctly test an IR sightglass
optic for its ability to withstand the static pressures associated
with an arc-flash event, a modified hydrostatic test must
be performed. Industry standards relating to this type of
testing require that the maximum operating pressure be increased
by 150% for the duration of the test.
As the maximum pressure seen in an
arc-flash event is 19 psi, a 150% increase equates to a minimum
static pressure requirement for an IR sightglass optic of
28 psi.
Thermoacoustic
Effects
 |
| Fig 13. Pressure
vents after an arc-flash event |
 |
Fig 14. Pressure relief plate
after
an arc-flash event
|
Arguably, the most destructive force seen
during an arc-flash event is the dynamic pressure increase,
known as the thermoacoustic wave. The thermoacoustic wave
is a function of the short-circuit current and is present
regardless of the equipment volume.
This shock wave can create impulse sound
levels well beyond OSHA's allowable limits. Forces from the
pressure wave can rupture eardrums, collapse lungs or cause
fatal injuries.
The thermoacoustic wave is used to operate
pressure relief systems built into arc-resistant switchgear,
which ultimately reduces the internal pressure in the equipment
as discussed in the previous section.
Clearly, a static pressure of 19 psi
will not result in such a ferocious operation. The buckling
shown in Fig. 15 is the direct result of the shock wave caused
under a 20kA for 0.1 sec arc-flash.
|
|
Fig 15. Buckling caused by
20kA arc-flash
|
“Arc-resistant” switchgear is
designed to withstand a combination of: static pressure, temperature
and dynamic pressure under an arc-fault event.
Heat-Flux Effects
Existing arc-flash tests can be used
to calculate a heat-flux level at the IR sightglass and are
indeed a “worst-case” scenario, as the testing
invariably includes pressure piling effects associated with
arc-resistant host switchgear.
| Example of IR sightglass
heat-flux calculation based on existing test data:
Background
IR sightglass is tested on a host piece
of arc-resistant equipment in accordance with C37.20.7-2001.
Nominal Minimum Voltage – 7.2kV
Maintained Fault Current – 40kA
Approximate Phase-to-Phase Arc-Gap –
5”
Distance of IR Sightglass Optic from Arc
– 17.75”
Arc Data (Calculated)*
Arc Column Area – 143.4421 sq. inches
Arc Diameter – 9.13187 inches
Arc Power in Watts – 5,937,500 Watts
Arc Power in Calories per Second –
1,418,469
Heat Flux on Surface of Arc – 1533.146
cal/cm2 – sec
Heat Flux on Sightglass – 86.52
cal/cm2 – sec
Total Calories per Sq. Cm.
at Sightglass - 43.2 86.52 cal/cm2 – sec
THIS EQUATES TO A LEVEL 4 HAZARD
/ RISK CATEGORY
*data acquired using Duke Power Heat-Flux calculator
|
As can be seen from the example above, it
is possible to test and calculate the resilience of an IR
sightglass optic for resistance to electric arc-flash in a
similar manner as the in-place arc rating in cal/cm2 standard
for faceshields.
Conclusion
IR sightglasses and ports are an invaluable
method for reducing the risk associated with infrared inspection
of energized equipment in accordance with OSHA and NFPA 70E.
However, manufacturing an infrared sightglass & port is
not as simple as installing an IR transmissive material, regardless
of its properties, into a mounting ring and subsequently into
a piece of equipment.
Due to the relatively recent introduction
of IR sightglass & port technology, current standards
do not properly address the requirements for correct testing
and validation of design and material selection. With arc-flash
safety and NFPA 70E being the primary driving factors behind
the installation of infrared sightglasses, any standard must
address the combined potential effects of:
• Heat flux at the sightglass location
• Maximum static pressure
• Thermoacoustic pressure
The selection of optic materials must be
regulated by the underlying philosophies associated with end-use
requirements, government legislation and in-place arc-flash
safety documents such as NFPA 70E.
Synthetic / Polymer materials should
be deemed acceptable for IR sightglass optics if the above
three tests can be successfully completed and the optic material
itself does not melt at less than 315°C in accordance
with NFPA 70E guidelines for arc-flash PPE utilizing synthetic
materials. Synthetic / Polymer materials which cannot withstand
the above tests should be limited to systems with a maximum
operating voltage of 50V.
Appendix
1

Notes:
1. Only install mesh, grid or port options
if the host equipment incorporates open louvers
2. Opening diameter during operation should
comply with local regulations to prevent foreign object
intrusion in accordance with EN60529 IP2X or IEEE C37.20.2
3. Crystal optic options installed into
Hazard/Risk Categories greater than 0 should have third
party arc-flash tests performed in order to assess maximum
heat flux endurance of the optic. Untested crystal optics
should not be used
4. Crystal optics versions shall incorporate
a locking metallic cover able to withstand daily impacts
in accordance with IEEE C37.20.2 A3.6
5. Thin film polymer optics may only be
used on Hazard/Risk Category Level 0 or as part of systems
with an operating voltage of 50V or less
6. Crystal optics installed into equipment
tested to arc-resistant requirements must have been subjected
to internal-arc tests of the applicable standard in order
to be acceptable
|